Chimney Requirments
|
|
- The boiler must be connected to a tile-lined chimney or to a Factory-Build Type HT approved chimney. The chimney must be in good condition. No other appliance should be connected to this flue. Consult your local building inspector for the chimney requirements and install the boiler in accordance with all applicable codes.
- Because of the very high efficiency of the Multi-Heat boilers the flue gas exhaust temperatures can be low enough to cause condensation in the chimney. This condensation may, over time, damage a masonry chimney. If you have condensation in your chimney, a stainless steel chimney liner should be installed inside the flue. A 5 inch diameter size for the MH 1.5 or a 6 inch diameter size for the MH 2.5 and MH 4.0 is appropriate.
- The chimney connection pipe must be placed on the exterior of the boiler’s flue collar.
- The chimney draft must be at least 0.025 inches water column and max. 0.10 inches water column. Excessively high chimney draft can be reduced by means of a draft stabilizer.
|
|